Control Parameter
No.
Name
Min.
28
1.01
WmUp_Delay
896
0
1.02
BL_On_Delay
0
0
1.03
BL_Off_Delay
0
Max_HT_ LT_
1.04
1
Occurrences
Sup_HT_Stg_
3
1.05
Delay
12
Sup_HT_2_
113
1.06
Lockout_T emp.
60
Sup_HT_1_
113
1.07
Lockout_T emp.
60
Compr_1_
81
Low_Temp_
1.08
80
Lockout
Compr_2_
81
1.09
Low_Temp_
80
Lockout
Compr_Min_
30
1.10
Off_Delay
60
Compr_Min_
30
1.11
Run_Time
60
Max_HP_
1.12
1
Occurrences
Max_LP_
1.13
1
Occurrences
Defrost_Sup_
1.14
0
HT_Option
Min_Time_ Be-
1.15
1
tween _Defrost
Max_Defrost_
2
1.16
Time
10
1.17
WmUp_Option
0
0
1.18
Sup_HT_1_ Diff
0
0
1.19
Sup_HT_2_ Diff
0
Sup_HT_1_
1.20
0
Latch_Option
Sup_HT_2_
1.21
0
Latch_Option
506457−01 05/10
Control Value
Default
Max.
Block 1 Heat Pump Heating Parameters
56
255
1792
8160
0
15
0
60
5
75
20
300
5
15
3
15
12
60
160
175
30
20
Y:DegF
144
175
40
20
255
254
−31
−30
255
254
−31
−30
150
255
300
510
120
255
240
510
3
8
3
8
1
1
2
3
3
5
15
25
0
2
8
15
2
3.75
W:DegF
12
15
3
3.75
W:DegF
0
1
0
1
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
Warm−up time delay. The time that the supplemental heat is held off
Counts
during the first demand of warm−up. This parameter is only used if the
D:Sec.
parameter 1.17 is set to option 1.
Counts
Blower on delay. The time before the blower turns on after a heating
B:Secs
demand.
Counts
Blower off delay. The time the blower stays on after the heating de-
B:Secs
mand is lost
Service output activation. Maximum Primary and Secondary Limit
occurrences stored before service relay is energized. If max value
Counts
is set, service output is disabled.
Note: Heating stage is not locked out.
Counts
Time delay between 1 & 2 stage of supplemental heat.
B:Secs
Temperature setpoint for lockout for the second bank of supplemental
Counts
heat.
Note: Temperature must be < or = to ECTO 1.07.
Counts
Temperature setpoint for lockout of first bank of supplemental heat.
Y: Deg.
Note: Temperature must be = to or > ECTO1.06.
Low ambient lockout for compressor 1. 254 value equals −30 ºF (−34ºC).
Counts
A value of 255 (−31ºF) will disable low ambient lockout function.
Y: Deg.
Note: This lockout is for heating only. Temperature must be < or = 1.09.
Low ambient lockout for compressor 2. 254 value equals −30 ºF (−34ºC).
Counts
A value of 255 (−31ºF) will disable low ambient lockout function.
Y: Deg.
Note: This lockout is for heating only. Temperature must be > or = 1.08.
Counts
Compressor minimum off delay. Used on 1 PH units. Also used on all
A:Sec
units after an alarm occurs.
Counts
Compressor minimum run time. Used on 3 PH units.
A:Sec
Maximum High Pressure occurrences stored before control locks off
Counts
compressor stage and energizes the service output. If max value is
set, lock−out and service output features are disabled.
Maximum Low Pressure occurrences stored before control locks off
compressor stage and energizes the service output. If max value is
Counts
set, lock−out and service output features are disabled.
Defrost options: 0: No supplemental heating during defrost. 1: Supple-
Option
mental heating on during defrost.
Minimum time allowed between defrost cycles.
1= 32 minutes
Option
2= 64 minutes
3=96 minutes
Counts
Maximum defrost time allowed.
Min
Warm−up mode option.
0−
Supplemental heat may be used during warm−up. Use depends
on outdoor temperature. See ECTO 1.06 and 1.07.
Option
1−
For the first demand cycle, lockout supplemental heat for the
first 30 minutes (default). Time is adjustable by changing the
parameter WARM−UP DLY # 1.01.
2−
For future use.
Supplemental heat stage 1 differential. Used in zone sensor applica-
Counts
tions.
Note: Differential temperature must be = to or < ECTO 1.19.
Supplemental heat stage 2 differential. Used in zone sensor applica-
Counts
tions.
Note: Differential temperature must be = to or > ECTO 1.18
Supplemental heat stage 1 latch option. Used in zone sensor applica-
tions.
Option
0: Latch Disabled
1: Latch Enabled
Supplemental heat stage 2 latch option. Used in zone sensor applica-
tions.
Option
0: Latch Disabled
1: Latch Enabled
Page 70
table continued on next page