Control Parameter
No.
Name
Min.
Service_
7.22
Output_
0
Control_Mode
0
0
Service_
7.23
Output_ SP
0
132
2
16
Service_
7.24
2
Output_ DB
1
64
506457−01 05/10
Control Value
Default
Max.
Block 7 System 2 Parameters (continued)
0
127
127
255
996
2000
100
100
51
−31
Y:DegF
13
255
102
2000
13
100
O:DegF
8
162
416
8160
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
A55 Service Output Control Mode = X + 32*Y + 16*Z
Input source = X:
0−
None. Standard Service Output based on alarms.
1−
Compressor 1 duty cycle. (Compressor crankcase heater func-
tion.)
On when OAT < = ECTO 7.23 and >= ECTO 7.24 seconds have
passed with compressor 1 off. Off when OAT > ECTO 7.23 + 3
deg F (fixed deadband) or < ECTO 7.24 seconds have passed
with compressor 1 off
2−
On when occupied.
3−
On when blower on,
4−
On when heating demand.
5−
On when cooling demand.
6−
On when heating or cooling demand.
7−
System RH (A55_P298_5 RH)
8−
System IAQ. (A55_P298_3 IAQ)
9−
System OAT (A55_P267_1/2 OAT)
10− Energy Recovery System (ERS) option.
11− SCR option for electric heat. DO−1 on with blower but off with
cooling.
Algorithm Y for input sources 7−9:
Option
0−
Hysteresis loop
On when input >= ECTO 7.23
Off when input < ECTO 7.23−ECTO 7.24
1−
Window
On when input is in range; >= ECTO
7.25
and <= ECTO 7.23 + ECTO 7.24
(Fixed 3−count hysteresis loop on rising
and falling edges of window.)
2−
Delayed−on
On when input is >= ECTO 7.23
for >= ECTO 7.24 seconds.
Off when input is < ECTO 7.23−3.
(Fixed 3−count hysteresis loop on edge.)
3−
Delayed−off
On when input is >= ECTO 7.23.
Off when input is < ECTO7.23 − 3
for >= ECTO 7.24 seconds.
(Fixed 3−count hysteresis loop on edge.)
Inversion Z:
0 − Output not inverted.
1 − Output inverted.
Counts
I:ppm
A55 service relay output setpoint.
P: %
Counts
I:ppm
P: %
A55 service relay output deadband or delay.
D:Sec.
Page 80
ON
OFF
7.23−7.24
ON
OFF
OFF
7.23
7.23 + 7.24
OFF
7.23
DELAY
7.24
DELAY
7.24
OFF
7.23
Graphs indicate output not
inverted. See figure 33.
table continued on next page
7.23
ON
ON