able 33. Air Delivery Setup for CAV w/Bypass for Changeover Zoning Applications
T
ECTO
No.
Name
Supply_VAV_
0.01
Control_ Mode
0.10
PID_P_ Constant
0.11
PID_I_Constant
PID_D_
0.12
Constant
0.13
CAVB_SMK_ SP
0.14
CAVB_ Vent_ SP
0.15
CAVB_ HT_ SP
0.16
CAVB_CL_SP
CAVB_Min_
Output_for
0.17
SMK_Vent_CL
CAVB_Min_
0.18
Output_ for HT
CAVB_Max_
0.19
Output
0.20
CAVB_ManRS
Supply_Static_
0.21
Shutdown_ SP
Supply_Static_
0.22
Lockout_Counts
Supply_VAV_
0.01
Control_ Mode
VAV_Press_ SMK_
0.02
SP
VAV_ Press_ Vent_
0.03
SP
0.04
VAV_ Press_ HT_SP
0.05
VAV_Press_ CL_ SP
VAV_Min_
Output_for_
0.06
CL_VT_ SMK.
VAV_Min_
0.07
Output_for_HT
VAV_Max_
0.08
Output
0.09
VAV_PID_ ManRS
506457−01 05/10
Default
Setting
Setting Required
0
1
Select (Recommend
17
default)
Select (Recommend
12
default)
Select (Recommend
0
default)
Select
1.00"w.c.
0−5"w.c.
Select
1.00"w.c.
0−5"w.c.
Select
1.00"w.c.
0−5"w.c.
Select
1.00"w.c.
0−5"w.c.
Select 20−100%
(Recommend
20%
default)
Select 20−100%
20%
(Recommend de-
fault)
Select 20−100%
(Recommend
100%
default)
Select 20−100%
52%
(Recommend
default)
Select
2.0"w.c.
0−5.0"w.c.
Select
0−5 counts (Recom-
3
mend default)
Air Delivery Setup For VAV Zoning Applications
0
63
Select
1.00"w.c.
0−5 "w.c.
Select
1.00"w.c.
0−5 "w.c.
Select
1.00"w.c.
0−5 "w.c.
Select
1.00"w.c.
0−5 "w.c.
Select
50%
30−100%
Select
50%
30−100%
Select 0−100%
100%
0−100%
Select 0−100%
(Recommend
60%
default)
Description
Sets PID control of bypass damper for all modes, ventilation, cooling, heating
and smoke alarms.
PID Proportional constant
PID Integral constant
PID derivative constant
Supply static pressure setpoint during smoke alarm. Typically 1 to 1.5"w.c.
Supply static pressure setpoint during ventilation only. Typically 1 to 1.5"w.c.
Supply static pressure setpoint during heating. Typically 1 to 1.5"w.c.
Supply static pressure setpoint during cooling. Typically 1 to 1.5"w.c.
Minimum output to bypass damper during smoke alarm, ventilation only and
cooling. Sets minimum air delivered. Bypass damper motor is set to 10 to 2
volts with 10 v being closed.
Minimum output to bypass damper during heating. Sets minimum delivered.
Maximum output to bypass damper for all modes. Sets the maximum air deliv-
ered.
Bypass damper manual reset value output. Output when blower is off.
Supply static shutdown setpoint. Unit will shutdown for ECTO 5.02 minutes if
duct pressure exceeds this value for 20 seconds
The number of occurrences before permanent lockout. Counter resets when
M2 resets.
A value of 0 will disable lockout.
Sets PID control of VFD all modes, ventilation, cooling, heating and smoke
alarms.
VAV supply static pressure setpoint during smoke detection.
VAV supply static pressure setpoint during ventilation.
VAV supply static pressure setpoint during heating.
VAV supply static pressure setpoint during cooling.
Supply minimum speed for cooling, ventilation or smoke.
If minimum is >= manual reset (ECTO 0.09), then manual reset used is
shifted to (ECTO 0.07 + ECTO 0.08) / 2
Supply minimum speed for heating.
If minimum is >= manual reset (ECTO 0.09), then manual reset used is
shifted to (ECTO 0.06 + ECTO 0.08) / 2
Supply maximum output.
Supply PID manual reset value.
Page 50
11.
Third−Party Zoning
table continued on next page