5. Low Ambient Fan Control
5.1.
High Efficiency A Box Fan Operation
The outdoor fan in a high efficiency A Box unit operates at three distinct speeds; High, Low and Extra−low. At higher outdoor
temperatures, (above 65F), the fan operates at high speed for a high cooling demand and at low speed for a low cooling or
de−humidification demand. At low outdoor temperatures the fan is off until the liquid pressure switch, S11 closes. Then the
fan runs at extra−low speed.
5.2.
Low Ambient Fan Cycling − Other Units
During low ambient conditions, various outdoor fans are cycled by liquid line pressure switches; S11, S84, S85 and S94. The
M2 unit controller will also de−energize fans due to low outdoor temperature. See Figure 4, for fan layouts and tables 9
through 14 for low ambient fan operations.