Control Parameter
No.
Name
Min.
0
Stg_3_StgUp_
4.21
Timer
0
0
Stg_4_StgUp_
4.22
Timer
0
0
4.23
StgDn_Timer
0
Zone_Sensor_
15
5.25
StartUp_ Delay
2
6.01
System_Mode
0
OCP_HT_
20
6.02
BkUp_ SP
95
UnOcp_HT_
20
6.03
BkUp_SP
95
Ocp_CL_
20
6.04
BkUp_ SP
95
UnOcp_CL_
20
6.05
BkUp_SP
95
Override_
0
6.06
Timer
0
4
6.07
HT_Stg_DB
1
4
6.08
CL_Stg_DB
1
0
6.09
Stg_1_HT_Diff
0
0
6.10
Stg_1_CL_Diff
0
0
6.11
Stg_2_HT_Diff
0
0
6.12
Stg_2_CL_Diff
0
0
6.13
Stg_3_CL_Diff
0
0
6.14
Stg_4_CL_Diff
0
Zone_Sensor Au-
8
tochangeover
6.15
2
DB_Min
506457−01 05/10
Control Value
Default
Max
Units
57
225
Counts
F:Sec
912
3600
57
225
Counts
F:Sec
912
3600
57
225
Counts
912
3600
F:Sec
15
225
Counts
2
30
C:Min.
0
12
Option
120
240
Counts
70
40
Z:DegF
160
240
Counts
60
40
Z:DegF
100
240
Counts
75
40
Z:DegF
60
240
Counts
85
40
Z:DegF
28
225
Counts
3584
28800
E: Sec
4
15
Counts
1
3.75
W:DegF
4
15
Counts
1
3.75
W:DegF
2
12
Counts
0.5
3
W:DegF
2
12
Counts
0.5
3
W:DegF
4
12
Counts
1
3
W:DegF
4
12
Counts
1
3
W:DegF
6
12
Counts
1.5
3
W:DegF
8
12
Counts
2
3
W:DegF
12
40
Counts
3
10
W:DegF
Description
Stage 3 stage up timer. The maximum time that cooling stage 2 runs
before calling cooling stage 3. Used in zone sensor applications.
Disabled if set to 0.
Stage 4 stage up timer. The maximum time that cooling stage 3 runs before call-
ing cooling stage 4. Used in zone sensor applications. Disabled if set to 0.
Time delay before a lower stage turns off following a higher stage termination.
Used in zone sensor applications.
General
Start−up demand delay. Holds off all unit operation zone sensor and CAVB ap-
plications. Hold off FAH−Reheat, FAC, FAH options and all GP outputs.
May be used to stagger unit start−ups. Does NOT delay demands in thermostat
mode.
System mode of operation.
Control Value
System Mode
0
Local Thermostat
1
Zone Sensor
2
Zone Sensor
3
Zone Sensor
4
Remote Demand
5
Remote Demand
6
Remote Demand
7
Remote Demand
Backup occupied heating setpoint. Used if the communications link is lost for 5
minutes between the M2 and NCP. Used only with zone sensor applications.
Setpoint temperature must be < or = (6.04 − 6.15).
Backup unoccupied heating setpoint. Used if the communications link is lost for 5
minutes between the M2 and NCP. Used only in zone sensor applications. Set-
point temperature must be < or = (6.05 − 6.15).
Backup occupied cooling setpoint. Used if the communications link is lost for 5
minutes between the M2 and NCP. Used only in zone sensor applications. Set-
point temperature must be > or = (6.02 + 6.15).
Backup unoccupied cooling setpoint. Used if the communications link is lost for 5
minutes between the M2 and NCP. Used only in zone sensor applications.
Setpoint temperature must be > or = (6.03 + 6.15).
After hours override timer. Only used on zone sensor applications without a Net-
work Control Panel (NPC).
Heating deadband. Used only with M2 zone sensor applications.
Deadband must be < or = 6.15 − 6.08.
Cooling deadband. Used only with zone sensor applications.
Deadband must be < or = 6.15 − 6.07.
Heating stage 1 differential. Used only with zone sensor applications.
Differential temperature must be < or = 6.11.
Cooling stage 1 differential. Used only with zone sensor applications.
Differential temperature must be < or = 6.12.
Heating stage 2 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.09.
Cooling stage 2 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.10 AND < or = 6.13.
Cooling stage 3 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.12 AND < or = 6.14.
Cooling stage 4 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.13.
Minimum autochangeover deadband temperature. Deadband must be > or =
(6.07 + 6.08).
Used in zone sensor applications.
Page 10
2.
Main Controller Operation
Backup Mode
None
None
Local Thermostat
Return Air Sensor
None
Local Thermostat
Return Air Sensor
Zone Sensor