Lennox Prodigy M2 Application Manual page 78

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Control Parameter
No.
Name
Min.
4
6.08
CL_Stg_DB
1
0
6.09
Stg_1_HT_Diff
0
0
6.10
Stg_1_CL_Diff
0
0
6.11
Stg_2_HT_Diff
0
0
6.12
Stg_2_CL_Diff
0
0
6.13
Stg_3_CL_Diff
0
0
6.14
Stg_4_CL_Diff
0
Zone_Sensor
8
6.15
Autochangeover
2
DB_Min
Autochangeover
15
6.16
_Delay
60
BL_Control-
6.17
0
Zone_Sensor
Zone_Sensor_
−20
6.18
Calibration
−5
Free_CL_ Lock-
112
6.19
out_SP
60
139
6.20
FAH_SP
70
5
6.21
FAH_Stg_DB
3
FAH_Min_
15
6.22
Cycle_ Time
120
Free_Cooling_
146
6.23
Supply_SP
65
0
6.24
Stg_3_HT_Diff
0
0
6.25
Stg_4_HT_Diff
0
Economizer_
97
6.26
Free_CL_SP
70
Economizer_
6.27
0
Profile
506457−01 05/10
Control Value
Default
Max.
Block 6 System 1 Parameters (continued)
4
15
1
3.75
W:DegF
2
12
0.5
3
W:DegF
2
12
0.5
3
W:DegF
4
12
1
3
W:DegF
4
12
1
3
W:DegF
6
12
1.5
3
W:DegF
8
12
2
3
W:DegF
12
40
3
10
W:DegF
75
225
300
900
0
1
0
20
0
5
W:DegF
161
160
Disabled
30
Y:DegF
138
183
40
X:DegF
Disabled
15
22
10
15
V:DegF
60
225
480
1800
161
176
55
45
X:Deg.F
6
12
1.5
3
W:DegF
8
12
2
3
W:DegF
191
2507
10
0
Y:DegF
2
2
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
Counts
Cooling deadband. Used only with zone sensor applications.
Deadband must be < or = 6.15 − 6.07.
Counts
Heating stage 1 differential. Used only with zone sensor applications.
Differential temperature must be < or = 6.11.
Counts
Cooling stage 1 differential. Used only with zone sensor applications.
Differential temperature must be < or = 6.12.
Counts
Heating stage 2 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.09.
Counts
Cooling stage 2 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.10 AND < or = 6.13.
Counts
Cooling stage 3 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.12 AND < or = 6.14.
Counts
Cooling stage 4 differential. Used only with zone sensor applications.
Differential temperature must be > or = 6.13.
Minimum autochangeover deadband temperature. Deadband must be
Counts
> or = (6.07 + 6.08).
Used in zone sensor applications.
Counts
Autochangeover time delay. Delay between heating and cooling
B: Sec
modes.
Blower control option for zone sensor applications during occupied
Option
periods. 0 = Blower cycles with demands 1 = Continuous blower
Zone sensor calibration offset.
Counts: −20 −16 −12 −8
Counts
Offset(ºF)−5
−4
−3
ºF is an offset added to the zone sensor reading. Example: If the zone
sensor is reading 2ºF high, it can be corrected by setting the count
value to −8 (−2ºF offset).
Free cooling lockout SP. Locks out free cooling when outdoor temper-
Counts
ature is below this value. Default value 161 disables free cooling lock-
out.
Fresh Air Heating setpoint. To enable FAH, set this to a value be-
Counts
tween 40F (183) and 70F(139). Minimum value (138) disables Fresh
Air Heating.
Counts
Fresh Air Heating stage deadband.
Counts
Fresh Air heating minimum cycle time.
C:Sec
Economizer modulates dampers to maintain supply air temperature
Counts
(RT6) at this setpoint during free cooling. DACC reset applies. See
ECTO 8.01−8.07.
Counts
Heating stage 3 differential temperature. Used only with zone sensor
applications. Differential temperature must >= ECTO 6.11.
Counts
Heating stage 4 differential temperature. Used only with zone sensor
applications. Differential temperature must >= ECTO 6.24.
A55 DIP switch selects temperature (TMP) or enthalpy (ODE) mode.
When in TMP mode, outdoor air is suitable for free−cooling when
Counts
OAT < ECTO for ECTO 41−70 degF, or when
OAT < RAT − ECTO for ECTO 0−40 degF.
This ECTO is not used in ODE mode.
OAT = OUTDOOR TEMPERATURE
Economizer operating profile during free cooling when compressor
cooling is on.
0 − Damper continues to modulate.
Option
1 − Damper opens to ECTO 5.23.
2 − Same as 1, but additionally holds off compressor cooling until
the damper has modulated to ECTO 5.23 value for 3 minutes.
Page 78
−4
0
4
8
12 16 20
−2
−1
0
1
2
3
4
RAT=RETURN TEMPERATURE
table continued on next page