Lennox Prodigy M2 Application Manual page 82

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Control Parameter
No.
Name
Min.
8.15
0
Exh_Fan_
8.16
0
Control
Exh_Fan_
0
8.17
Stg_1_ SP
0
Exh_Fan_
0
8.18
Stg_2_ SP
0
Exh_Fan_
0
8.19
SP_for _SMK
0.5
Staged_SMK
0
0
8.20
Exh_Fan_SP
−0.5
0
Stage_1_SP
−0.5
0
8.21
Exh_Fan_Min
0
0
Staged_1_DB
0
Exh_Fan_
0
8.22
ManRS
0
Stg_1_Off_
0
Delay
Exh_Fan_PID_
8.23
0
P_Constant
506457−01 05/10
Control Value
Default
Max.
Block 8 System 3 Parameters (continued)
0
255
0
23
50
100
50
100
100
100
100
100
50
255
−0.3
0.5
50
100
50
255
−0.3
0.5
50
100
−0.3
0.5
10
255
10
100
10
100
0.04
1.0
50
100
50
100
100
200
20
255
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
Counts
Reserved.
Single stage (controlled by A55_P265−2 output)
Mode Enable
0−
Blower
1−
Always
2−
OCP
3−
Blower
4−
Always
5−
Occupied
6−
Blower
7−
A133_P194−1 A133_P194−7
Two stage exhaust fan (controlled by A55_P265−2 & A133_p194−5
outputs)
Mode Enable
8−
Blower
9−
Always
10−
Occupied
11−
Blower
12−
Always
13−
Occupied
14−
Blower
15−
A133_P194−1 A133_P194−7 A133_P194−7
Option
For option 9−15, Stage 2 will not turn on until ECTO 8.25 seconds after
stage 1. Stage 1 won't turn off until ECTO 8.22 seconds after stage 2
turns off.
VFD (PID) controlled Exhaust Fan with on/off cycling at minimum
speed (Cycled by A55_P265−2 and Speed controlled by VFD)
Mode Enable
16
Always
17−
Occupied
18−
Blower
19−
A133_P194−1 A133_P194−7
Min. speed cycling: On at 10% over setpoint. Off after 30 seconds at
minimum speed. Minimum 30 seconds off.
VFD (PID) controlled Exhaust Fan (Always on when enabled)
(Cycled by A55_P265−2 and Speed controlled by VFD)
Mode Enable
20
Always
21
Occupied
22
Blower
23−
A133_P194−1 A133_P194−7
Always on at least minimum speed when enabled.
Counts
Speed setpoint for stage 1 exhaust fan when using a VFD for control-
P:%
ling exhaust fan in staged mode.
Counts
Speed setpoint for stage 2 exhaust fan when using a VFD for control-
P:%
ling exhaust fan in staged mode.
Counts
Exhaust fan smoke mode setpoint for PID option control
M:"w.c.
Staged setpoint for during smoke alarm.
P:%
Value used depends on smoke mode (ECTO 5.01)
Counts
Exhaust fan setpoint for PID option control
M:"w.c.
P:%
Stage 1 setpoint.
M:"w.c.
Counts
Exhaust fan minimum speed.
P:%
P:%
Staged 1 deadband.
L:"w.c.
Counts
Exhaust fan PID loop manual reset value.
P: %
A:Sec.
Stage 1 off−delay. (Only used for 2 stage operation)
Exhaust fan PID loop proportional constant. The P constant must be
Counts
limited to 127. Recommended setting = 17.
Page 82
Input 1
D_POS
A133_P194−1
A133_P194−1
A133_P194−1
A133_P194−7
A133_P194−7
A133_P194−7
Input 1
Input 2
D_POS
D_POS
A133_P194−1 A133_P194−2
A133_P194−1 A133_P194−2
A133_P194−1 A133_P194−2
A133_P194−7 A133_P194−7
A133_P194−7 A133_P194−7
A133_P194−7 A133_P194−7
Analog Input
A133_P194−7
A133_P194−7
A133_P194−7
Analog Input
A133_P194−7
A133_P194−7
A133_P194−7
table continued on next page
USE ECTO 8.20
AND 8.21 FOR
SETPOINT AND
DEADBAND.
USE ECTO 8.17
FOR 0−10VDC
STAGE 1 OUTPUT
IF A133 (VAV)
PRESENT.
USE ECTO 8.20−8.25
FOR STAGE
SETPOINTS,
DEADBANDS AND
STAGE DELAYS.
USE ECTO 8.17
FOR 0−10VDC
STAGE 1 OUTPUT.
USE ECTO 8.18
FOR 0−10VDC
STAGE 2 OUTPUT.
USE ECTO
8.19−8.25 FOR
SETPOINT AND
PID CONSTANTS.
USE ECTO
8.20−8.25 FOR
SETPOINT AND
PID CONSTANTS.