Opp Setting - R&S NGE100B Series User Manual

Hide thumbs Also See for NGE100B Series:
Table of Contents

Advertisement

®
R&S
NGE100B
Example:
[SOURce:]VOLTage:PROTection:CLEar
This command resets the OVP state of the selected channel. If the OVP has tripped
the OVP message on the display will be cleared for the selected channel.
Usage:

6.5.9 OPP Setting

[SOURce:]POWer:PROTection:LEVel <Power>
This command defines or queries the OPP value of the previous selected channel.
Parameters:
<Power>
Example:
[SOURce:]POWer:PROTection:TRIPped?
This command queries the OPP tripped status of the previous selected channel
Return values:
<arg0>
User Manual 5601.1343.02 ─ 04
INST OUT1
VOLT:PROT:LEV 5
Set the OVP value of Ch 1 to 5 V.
VOLT:PROT:LEV?
Return the selected channel OVP value.
Event
{<Voltage> | MIN | MAX}
<Voltage>
Set the OPP value in the range of 0 W up to 32 W (adjustable in
100 mW steps)
MIN
Set the OPP value to minimum.
MAX
Set the OPP value to maximum
Default unit: W
INST OUT1
POW:PROT:LEV 5
Set the OPP value of channel 1 to 5 W.
POW:PROT:LEV? -> 5
Return the selected channel OPP value.
1 | 0
1
OPP is tripped.
0
OPP is not tripped.
Remote Control
Remote Control - Commands
87

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nge103bNge102b

Table of Contents