. . .Operation
. . .Parameter descriptions

Menu: Communication

Menu / parameter
Communication
. . .HART
. . .Modbus
. . .Profibus
Communication / . . .HART
Device Address
Loop Current Mode
HART Tag
HART Long Tag
HART Descriptor
HART Message
HART Manuf. ID
HART Device ID
HART Find
Last HART Command
Description
Selection of submenu '...HART' using
Selection of submenu '...Modbus' using
Selection of submenu '...Profibus' using
Selection of HART device address.
Note
The HART protocol has provisions for creating a bus with up to 15 devices (1 to 15)).
If an address greater than 0 is set, the device operates in multidrop mode. The current output 31 / 32 / Uco is
fixed to 4 mA. HART communication takes place only through current output 31 / 32 / Uco.
Selection of the operating mode for current output with HART communication.
• Multidrop Fixed
• Normal Signaling
Entry of a HART TAG number as unique identifier for the device.
Alphanumeric, a maximum of 8 characters, upper case only, no special characters.
Entry of a HART TAG number as unique identifier for the device.
Alphanumeric, maximum of 32 characters, ASCII
Only starting from HART version 7!
Entry of a HART descriptor.
Alphanumeric, a maximum of 16 characters, upper case only, no special characters.
Display of the alphanumeric TAG number.
Display of the HART manufacturer ID. ABB = 26
Display of the HART device ID.
Select whether the transmitter must respond to the HART command 73 (Find Device).
• Off: The transmitter does not respond to command 73.
• Once: The transmitter responds once to command 73.
• Continuous: The transmitter always responds to command 73.
Display of the most recently sent HART command.
.
.
.