42
F EM63 0 | E L EC TR OM AG N E T I C FLOWM E T E R | O I/F E M6 3 0-EN RE V. A
6
. . .Electrical connections
. . .Pin assignment
Active current output V3 / V4
When the 'loop power supply 24 V DC, blue' plug-in card is
used, the current output on the plug-in card can also be wired
as the active current output.
I
A
B
'Loop power supply (blue)' plug-in card in slot 1
A
'Passive current output (red)' plug-in card in slot 2
B
Figure 51 Active current output V3 / V4 (example)
Digital input V3 / V4 active
When the 'loop power supply 24 V DC, blue' plug-in card is
used, the current output on the plug-in card can also be wired
as the active current output.
I
A
B
'Loop power supply (blue)' plug-in card in slot 1
A
'Passive digital input (yellow)' plug-in card in slot 2
B
Figure 52 Active digital output V3 / V4 (example)
E
+24 V
DC
, max. 25 mA
V1+
0V
V2-
V3+
V4-
G11742-01
E
+24 V
DC
, max. 25 mA
V1+
0V
V2-
V3+
V4-
G11914
Connection versions digital output 41 / 42, 51 / 52
Depending on the wiring of digital outputs DO 41 / 42 and 51
/ 52, they can be used parallel or only individually. The
electrical isolation between the digital outputs also depends
on the wiring.
A
I
E
41+
012345
51+
42-/
52-
B
I
E
41+
51+
42-/
52-
C
I
E
41+
51+
42-/
52-
D
I
E
41+
51+
42-/
52-
Figure 53 Connection versions digital
output 41 / 42 and 51 / 52
DO 41 / 42 and 51 / 52 can be
used parallel
Yes
A
Yes
B
No, only DO 41 / 42 can be used
C
No, only DO 51 / 52 can be used
D
Table 1 Connection versions digital output
U
+
B
R
B
1
R
B
2
012345
U
B
1
+
012345
R
B
2
012345
R
B
U
B
+
012345
R
B
U
B
+
012345
R
B
DO 41 / 42 and 51 / 52
electrically isolated
No
Yes
No
No
-
-
-
-
G12392