FE M63 0 | E L EC TR OM AG N E T I C FLOWM E T E R | O I/F E M6 3 0-EN RE V. A
8
. . .Operation
. . .Parameter descriptions

Menu: Input/output

Menu / parameter
Input/Output
...Curr.Out 31/32
...Curr.Out V1/V2
...Curr.Out V3/V4
...Dig.Out 41/42
...Dig.Out 51/52
...Dig.Out V1/V2
...Dig. Out V3/V4
...Dig.In V1/V2
...Dig.In V3/V4
Input/Output / ...Curr.Out 31/32
Input/Output / ...Curr.Out V1/V2
Input/Output / ...Curr.Out V3/V4
Output Value
Curr.Out Mode
Curr.Out at Alarm
Low Alarm
High Alarm
Curr.Out > 20.5mA
Description
Selection of submenu '...Curr.Out 31/32' using
Selection of submenu '...Curr.Out V1/V2' using
Selection of submenu '...Curr.Out V3/V4' using
Selection of submenu '...Dig.Out 41/42' using
Selection of submenu '...Dig.Out 51/52' using
Selection of submenu '...Dig.Out V1/V2' using
Selection of submenu '...Dig. Out V3/V4' using
Selection of submenu '...Dig.In V1/V2' using
Selection of submenu '...Dig.In V3/V4' using
Selection of process variable issued at the corresponding current output.
• Qm [%]: The current output provides the mass flow in percent.
• Qv [%]: The current output provides the volume flow in percent.
• Conductivity[µS/cm]: The current output provides the conductivity in μS/cm..
The current outputs V1 / V2 and V3 / V4 are only available if the corresponding plug-in cards are available!
• Select the operating mode for the current output.
• '4-20mA FWD' Output flow rate in forward flow:
4 mA = no flow
20 mA = maximum flow
• '4-12-20 mA': Output flow rate in forward and reverse flow:
4 mA = maximum flow in reverse flow
12 mA = no flow
20 mA = maximum flow in forward flow
• '4-20mA FWD/REV': Output flow rate in forward and reverse flow without distinction of flow direction:
4 mA = no flow
20 mA = maximum flow
Default setting: 4-20mA FWD/REV.
Selection of status of the current output in error condition.
The output 'low' or 'high' current is set in the subsequent menu.
Default setting: High Alarm.
Sets the current for Low Alarm.
Sets the current for High Alarm.
Behavior of current output if 20.5 mA is exceeded.
• Hold Last Value: The last measured value is retained and issued.
• High Alarm: The high alarm current is issued.
• Low Alarm: The low alarm current is issued.
Default setting: Hold Last Value.
.
.
.
.
.
.
.
.
.