. . .Diagnosis / error messages
. . .Error messages
Operation outside of specifications (Out Of Spec .)
Error no . / Range
Text on the LCD display
Inhouse temp. alarm.
S065.044 / operation
Reduce ambient temperature.
EPD alarm.
S064.041 / operation
Secure pipe is completely filled.
TFE alarm.
S063.040 / operation
Secure pipe is completely filled.
Sensor temp. limits alarm.
S062.039 / operation
Change limits or change fluid
temperature.
Conductivity limits alarm.
S061.038 / operation
Change limits or Check
application.
Gas bubble alarm.
S060.037 / operation
Check conditions of application.
Curr.Out 31 / 32 is saturated.
S052.016 / operation
CO process value out of range.
Adapt Qmax.
Curr.Out V1 / V2, V3 / V4
saturated.
S051.017 / operation
CO process value out of range.
Adapt Qmax.
Option Card 1 com error.
S049.019 / electronics
Defective Card. Check Card 1.
Call Service.
Option Card 2 com error.
S048.020 / electronics
Defective Card. Check Card 2.
Call Service.
Pulse output is cut off.
S047.015 / operation
Wrong config. Check pulse out
configuration.
Mass flowrate exceeds limits.
S046.000 / operation
Check flowrate and alarm limits.
Volume flowrate exceeds limits.
S044.001 / operation
Check flowrate and alarm limits.
Cause
Measuring medium or ambient temperature
is outside the spec.
Sensor not filled.
Alarm of the complete filling electrode, but
incorrect, because the sensor is not
completely filled.
The measuring medium temperature is
outside the temperature limit.
The conductivity of the measuring medium is
outside the limit values.
Gas bubbles in the measuring medium.
The selected process value of the current
output 31/32 is outside the measuring
range.
The selected process value of the current
output V1 / V2 or V3 / V4 is outside the
measuring range.
Broken hardware of the motherboard or
option card.
EMC interference
Broken hardware of the motherboard or
option card.
EMC interference
The calculated output pulse or the calculated
output frequency is above the configured
cutoff frequency.
The mass flow is below or above the
configured limit values 'Qm Massflow Min'
and 'Qm Massflow Max'.
The volume flow rate is below or above the
configured limit values 'Qv Volumeflow Min'
and 'Qv Volumeflow Max'.
Remedy
Check process conditions, reduce
temperature.
Check if pipe is empty.
Make sure that the sensor is completely filled.
Check installation and process conditions.
Check process conditions and adjust alarm
threshold.
Check process conditions and adjust alarm
threshold.
Check the process conditions.
Adjust measuring range.
Adjust measuring range.
Check / replace option card in slot 1.
Please contact the service department.
Check / replace option card in slot 2.
Please contact the service department.
Check configuration for the output pulse.
Check the parameterization in menu 'Process
Alarm / ...Alarm Limits' and adjust as needed.
Check volume flow rate.
Check the parameterization in menu 'Process
Alarm / ...Alarm Limits' and adjust as needed.
Check volume flow rate.