FE M63 0 | E L EC TR OM AG N E T I C FLOWM E T E R | O I/F E M6 3 0-EN RE V. A
5
. . .Installation

Installing the plug-in cards

WARNING
Loss of Ex Approval!
Loss of Ex Approval due to retrofitting of plug-in cards on devices for use in potentially explosive atmospheres.
• Devices for use in potentially explosive atmospheres may not be retrofitted with plug-in cards.
• If devices are to be used in potentially explosive atmospheres, the required plug-in cards must be specified when the
order is placed.
Optional plug-in cards
The transmitter has two slots (OC1, OC2) into which plug-in cards can be inserted to extend inputs and outputs. The slots are
located on the transmitter motherboard and can be accessed after removing the front housing cover.
Plug-in card
*The 'Number' column indicates the maximum number of plug-in cards of the same type that can be used.
Description
Current output, 4 to 20 mA passive (red)
Order no.: 3KQZ400029U0100
Passive digital output (green)
Order no.: 3KQZ400030U0100
Passive digital input (yellow)
Order no.: 3KQZ400032U0100
Loop power supply 24 V DC (blue)
Order no.: 3KQZ400031U0100
Modbus RTU RS485 (white)
Order no.: 3KQZ400028U0100
Profibus DP (white)
Order no.: 3KQZ400027U0100
Quantity*
Maximum of two plug-in cards
Maximum of one plug-in card
Maximum of one plug-in card
Maximum of one plug-in card
Maximum of one plug-in card
Maximum of one plug-in card
25