ABB ProcessMaster FEM630 Operating Instructions Manual page 115

Electromagnetic flowmeter
Hide thumbs Also See for ProcessMaster FEM630:
Table of Contents

Advertisement

FE M63 0 | E L EC TR OM AG N E T I C FLOWM E T E R | O I/F E M6 3 0-EN RE V. A
9
. . .Diagnosis / error messages
. . .Overview
Error no . / Range
Error text
Inhouse temp. alarm.
S065.044 / operation
Reduce ambient
temperature.
EPD alarm.
S064.041 / operation
Secure pipe is
completely filled.
TFE alarm.
S063.040 / operation
Secure pipe is
completely filled.
Sensor temp. limits
alarm.
S062.039 / operation
Change limits or
change fluid
temperature.
Conductivity limits
alarm.
S061.038 / operation
Change limits or
Check application.
Gas bubble alarm.
S060.037 / operation
Check conditions of
application.
Curr.Out 31 / 32 is
saturated.
S052.016 / operation
CO process value out
of range. Adapt
Qmax.
Curr.Out V1 / V2, V3
/ V4 saturated.
S051.017 / operation
CO process value out
of range. Adapt
Qmax.
Option Card 1 com
error.
S049.019 /
Defective Card.
electronics
Check Card 1. Call
Service.
Option Card 2 com
error.
S048.020 /
Defective Card.
electronics
Check Card 2. Call
Service.
Current output
Digital output
Current value - no
No Answer
change.
Alarm - configured as in
Alarm, if DO as 'Logic /
menu 'Curr. at EPD
Alarm Signal / EPD
Alarm'.
Alarm' is configured
Alarm - configured as in
Alarm, if DO as 'Logic /
menu 'Curr. at TFE
Alarm Signal / TFE
Alarm'.
Alarm' is configured
Current value - no
No Answer
change.
Current value - no
Alarm, if DO as 'Logic /
change.
Alarm Signal /
Conductivity' is
configured
Current value - no
Alarm, if DO as 'Logic /
change.
Alarm Signal / Gas
bubble Alarm' is
configured
Alarm - configured as in
Current value - no
menu '„Curr.Out >
change.
20.5mA'.
Does not react anymore Current value - no
change.
Does not react anymore Current value - no
change.
Pulse output
LCD display
Current value -
No Answer
no change.
0 Hz
0 %
Current value - no
Current value -
change.
no change.
Current value - no
Current value -
change.
no change.
Current value - no
Current value -
change.
no change.
Current value - no
Current value -
change.
no change.
Current value - no
Current value -
change.
no change.
Current value - no
Current value -
change.
no change.
Current value - no
Current value -
change.
no change.
115
Error maskable?
Menu '...Group
Masking'.
Menu '...Group
Masking'.
Menu '...Group
Masking'.
Menu '...Group
Masking'.
Menu '...Group
Masking'.
Menu '...Group
Masking'.
Menu '...Group
Masking'.
Menu '...Group
Masking'.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents