56
F EM63 0 | E L EC TR OM AG N E T I C FLOWM E T E R | O I/F E M6 3 0-EN RE V. A
. . .7
Commissioning
...Parameterization via the menu function
Easy Setup
Easy Setup
Exit
5
Use
/
to select 'Easy Setup'.
6
Confirm the selection with
Easy Setup
Language
Next
7
Use
to call up the edit mode.
8
Use /
to select the desired language.
9
Confirm the selection with
Easy Setup
Unit Volumeflow Qv
Next
10 Use
to call up the edit mode.
11 Use
/
to select the desired unit for the volume
flow rate.
12 Confirm the selection with
Menu
Select
.
Language
Edit
.
ugal/s
Edit
.
Easy Setup
Qv Max 1
Next
13 Use
to call up the edit mode.
14 Use
/
to set the desired upper range value.
15 Confirm the selection with
The device is factory calibrated to the flow range end value
QmaxDN, unless other customer information is available. The
ideal upper range values are those which correspond to a flow
velocity of 6.5 to 10 ft/s (2 to 3 m/s) (0.2 to 0.3 × Q
The adjustable upper range values are listed in the table at
Measuring range table on page 59.
Easy Setup
Unit Vol. Totalizer
Next
16 Use
to call up the edit mode.
17 Use
/
to select the desired unit for the volume
totalizer.
18 Confirm the selection with
Easy Setup
Pulses per Unit
Next
19 Use
to call up the edit mode.
20 Use
/
to select the desired pulse per unit for the
pulse output.
21 Confirm the selection with
25.000 ugal/s
Edit
.
DN)
max
ugal/s
Edit
.
10.000/ft³
Edit
.