ABB ProcessMaster FEM630 Operating Instructions Manual page 82

Electromagnetic flowmeter
Hide thumbs Also See for ProcessMaster FEM630:
Table of Contents

Advertisement

82
F EM63 0 | E L EC TR OM AG N E T I C FLOWM E T E R | O I/F E M6 3 0-EN RE V. A
8
. . .Operation
. . .Parameter descriptions
Menu / parameter
Device Setup / . . .Sensor
Qv Max DN
Qv Max 1
Qv Max 2
Qv Range Mode
Sensor Location Tag
Sensor Tag
. . .Operating Mode
Device Setup / . . .Sensor / . . .Operating Mode
Flow Direction
Flow Indication
The value provides the lower volume flow at a flow velocity of 32.8 ft/s (10 m/s).
The value is set automatically via the selected nominal diameter.
Setting the upper range value 1 (Measuring range = 0 to Qv Max 1) for the volume flow for forward flow and
reverse flow .
Default setting: 1 × Q
DN
max
Setting the upper range value 2 (Measuring range = 0 to Qv Max 2) for the volume flow for forward flow and
reverse flow .
This parameter is only available if the value 'Max2 active' has been selected for the parameter 'Qv Range Mode'.
Default setting: 1 × Q
DN
max
Manual switchover between the measuring ranges (Max1 active / Max2 active) for the volume flow
measurement. This parameter is only available if the value Qm and Qv or Range Mode Confighas been selected
for the parameter 'Qv only'
Entry of the measuring point tag for the sensor.
Alphanumeric, max. 20 characters
Enter the tag number of the sensor.
Alphanumeric, max. 20 characters.
Selection of submenu '...Operating Mode' using
Set the measuring direction for the sensor.
As delivered, the device measures and counts in both flow directions.
• Forward & Reverse: The device measures in both flow directions.
• Forward only: The device measures only forward flow direction.
• Reverse only: The device measures only reverse flow direction.
Default setting: Forward & Reverse
Inversion of the displayed flow direction.
Default setting: Normal
.