. . .Operation
. . .Parameter descriptions
Menu / parameter
Input/Output / ...Dig.Out 41/42 / ...Setup Pulse Output
Output Value Pulse
Pulses per Unit
Pulse Width
Input/Output / ...Dig.Out 41/42 / ...Setup Freq Output
Output Value Freq.
Upper Frequency
Input/Output / ...Dig.Out 41/42 / ...Setup Logic Output
Logic Output Action
Active Mode
Description
Selection of process variable that is issued via the pulse output.
• Off: The pulse output is deactivated.
• Pulse Mass Flow: The pulse output indicates the mass flow.
• Pulse Volume Flow: The pulse output indicates the volume flow.
Sets the pulses per mass unit or volume unit (see table Available units on page 77) and the pulse width for the
pulse output.
The potential pulse width depends on the configured pulse value and is calculated dynamically.
Selection of process variable that is issued via the frequency output.
• Off: The pulse output is deactivated.
• Pulse Mass Flow: The pulse output indicates the mass flow.
• Pulse Volume Flow: The pulse output indicates the volume flow.
Sets the frequency for the upper range value. The entered value corresponds to 100 % flow.
Selection of binary output function.
• Off: The binary output is deactivated.
• F/R Signal: The binary output signals the flow direction.
• Alarm Signal: The binary output indicates an active alarm. The alarm is selected in the '„...Alarm Config'
menu.
• Dual Range: The binary output is activated when measuring range 2 (Qm Max 2 / Qv Max 2) is selected.
This selection is only available if the parameter 'Dual Range' has been configured to Qm or Qv.
• Batch End Contact: The binary output is activated when the set fill quantity is reached (only if the FillMass
function is activated).
Select switching properties for the binary output.
• Active High: Normally open
• Active Low: Normally closed
Default setting: Active High.
89