5.6 Mains Power Connections – Fig 5.9
Fuse,
1A, Type T
Line
Neutral
Terminal Block E
Caution. Use fuse rating – 1A (max.) type T.
Fig. 5.9 Mains Power Supply
5.7 Relay Output Board Connections – Fig. 5.10
Note.
• The maximum total combined current flowing through the
relays is 36A. The maximum individual relay current is 5A.
• The polarity is set up during I/O module configuration –
see Section 4.7.2, 3-Relay and 6-Relay Modules.
17
14
11
18
15
12
19
16
13
Terminal Block C or D
Note. Relay contacts are fitted with arc
suppression components as standard.
Fig. 5.10 Relay Connections

5.8 Hybrid I/O Module Connections

5.8.1 Digital Output Connections – Fig 5.11
Six digital outputs are provided on the Hybrid option board.
do1
9
do2
10
do3
11
do4
12
do5
13
do6
14
COM
15
COM
16
Information.
Voltage level 5V. Load: 450Ω min. 15kΩ max.
Note. Refer to Fig. 5.5 for terminal numbers.
Fig. 5.11 Digital Output Connections
L
85 – 265V
N
50/60Hz
7
4
1
8
5
2
9
6
3
Digital Output
Load
Common
5.8.2 Digital Input Connections – Fig 5.12
Six digital inputs are provided on Hybrid option boards.
Terminal Blocks C or D
1
di1
2
di2
3
di3
4
di4
5
di5
6
di6
7
COM
8
COM
Input State
Switch Input
Logic Input
or
0V
or
5V
Fig. 5.12 Digital Input Connections
5.8.3 Analog Output Connections – Fig 5.13
Two analog outputs are provided on the Hybrid option board.
17
18
19
20
Fig. 5.13 Analog Output Connections
5 INSTALLATION
or
5V
0V
Logic State
Dxx active
Dxx in-active
+
a01
+
a02
77