Specifications

8.2 Mains Supply

Mains supply (L1, L2, L3)
Supply voltage
Mains voltage low/mains voltage dropout:
During low mains voltage or a mains dropout, the frequency converter continues until the DC-link voltage drops below the
minimum stop level. The minimum stop level corresponds typically to 15% below the frequency converter's lowest rated supply
voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest
rated supply voltage.
Supply frequency
Maximum imbalance temporary between mains phases
True power factor (λ)
Displacement power factor (cos Φ) near unity
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 480/600 V.

8.3 Motor Output and Motor Data

Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
1) Dependent on voltage and power.
Torque characteristics
Starting torque (constant torque)
Starting torque
Overload torque (constant torque)
1) Percentage relates to the frequency converter's nominal torque.
MG21A402
Operating Guide
Danfoss A/S © 11/2016 All rights reserved.
380–480 V ±10%, 525–690 V ±10%
50/60 Hz ±5%
3.0% of rated supply voltage
±0.9 nominal at rated load
Maximum 1 time/2 minutes
Overvoltage category III/pollution degree 2
0–100% of supply voltage
Maximum 160% for 60 s
Maximum 180% up to 0.5 s
Maximum 160% for 60 s
(>0.98)
8
8
1)
0–590 Hz
Unlimited
0.01–3600 s
1)
1)
1)
65