Signals; T_Tcmd Function Block; Function Block; Functionality - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Section 3
Basic functions
3.12.6.3
3.12.7
3.12.7.1
3.12.7.2
72
LD0.<function>.Str.dirGeneral or LD0.<function>.Dir.dirGeneral data attribute sent
by another device.
In case the GOOSERCV_ENUM function block does not receive the value from the
sending device or it is invalid, the default value (0) is used in function outputs.
The outputs FWD and REV are extracted from the enumerated input value.

Signals

Table 63:
T_DIR Input signals
Name
Type
DIR
Enum
Table 64:
T_DIR Output signals
Name
Type
FWD
BOOLEAN
REV
BOOLEAN

T_TCMD function block

Function block

GUID-1CE485AE-2BCA-4D1E-92F5-417340F2589F V1 EN
Figure 41:
Function block

Functionality

The T_TCMD function is used to convert enumerated input signal to Boolean output
signals.
Table 65:
Conversion from enumerated to Boolean
IN
0
1
2
x
Default
0
Default
0
0
RAISE
FALSE
FALSE
TRUE
FALSE
1MRS758407 B
Description
Input signal
Description
Direction forward
Direction backward
LOWER
FALSE
TRUE
FALSE
FALSE
SMU615
Technical Manual