Settings; Monitored Data - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
3.15.2.4
3.15.2.5
SMU615
Technical Manual

Settings

Table 162:
Port mode settings
Parameter
Values (Range) Unit
Port 1 Mode
Off
On
Port 2 Mode
Off
On
Port 3 Mode
Off
On

Monitored data

Monitored data is available in six locations.
Monitoring/Communication/Ethernet/Activity/CH1LIV
Monitoring/Communication/Ethernet/Activity/CH2LIV
Monitoring/Communication/Ethernet/Activity/CH3LIV
Monitoring/Communication/Ethernet/Link statuses/LNK1LIV
Monitoring/Communication/Ethernet/Link statuses/LNK2LIV
Monitoring/Communication/Ethernet/Link statuses/LNK3LIV
Step
Default Description
On
Mode selection for rear port(s). If port is
not used, it can be set to "Off". Port
cannot be set to "Off" when
mode is "HSR" or "PRP" and port is one
of the redundant ports (LAN A or LAN B)
or when port is used for line differential
communication.
On
Mode selection for rear port(s). If port is
not used, it can be set to "Off". Port
cannot be set to "Off" when
mode is "HSR" or "PRP" and port is one
of the redundant ports (LAN A or LAN B).
On
Mode selection for rear port(s). If port is
not used, it can be set to "Off". Port
cannot be set to "Off" when
mode is "HSR" or "PRP" and port is one
of the redundant ports (LAN A or LAN B).
Section 3
Basic functions
Redundant
Redundant
Redundant
117