T_Health Function Block; Function Block; Functionality; Signals - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Section 3
Basic functions
3.12.4
3.12.4.1
3.12.4.2
3.12.4.3
70

T_HEALTH function block

Function block

GUID-B5FCAE66-8026-4D5F-AC38-028E5A8171BB V1 EN
Figure 38:
Function block

Functionality

The T_HEALTH function evaluates enumerated data of "Health" data attribute. This
function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs OK, WARNING and ALARM are extracted from the enumerated input
value. Only one of the outputs can be active at a time. In case the
GOOSERCV_ENUM function block does not receive the value from the sending
device or it is invalid, the default value (0) is used and the ALARM is activated in the
T_HEALTH function block.

Signals

Table 59:
T_HEALTH Input signals
Name
Type
IN1
Any
Table 60:
T_HEALTH Output signals
Name
Type
OK
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN
Default
Description
0
Input signal
Description
Output signal
Output signal
Output signal
1MRS758407 B
SMU615
Technical Manual