Station Authority Level "L,R; Station Authority Level "L,R,L+R - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
3.13.8.4
Table 146:
Station authority "L,R" using CONTROL function block
L/R control
Control FB input
CTRL.LLN0.LocSta
CTRL_OFF
CTRL_LOC
CTRL_STA
CTRL_REM
CTRL_ALL
1) Client IEC 61850 command originator category check is not performed.
3.13.8.5
SMU615
Technical Manual

Station authority level "L,R"

In this scenario only local or remote control access is allowed. Control access with
IEC 61850 command originator category station is interpreted as remote access. There
is no multilevel access.
REMOTE
IEC 61850
IEC 61850
IEC 61850
remote
remote
remote
IED
GUID-08BACCE4-AF4A-4150-A01A-49FBEE63B438 V1 EN
Figure 72:
Station authority is "L,R"
When station authority level "L,R" is used, control access can be selected using the
CONTROL function block. IEC 61850 data object CTRL.LLN0.LocSta and
CONTROL function block inputs CTRL_STA and CTRL_ALL are not applicable for
this station authority level.
L/R control status
CTRL.LLN0.MltLev
N/A
FALSE
N/A
FALSE
N/A
FALSE
N/A
FALSE
N/A
FALSE

Station authority level "L,R,L+R"

Station authority level "L,R, L+R" adds multilevel access support. Control access can
also be simultaneously permitted from local or remote location. Simultaneous local or
remote control operation is not allowed as one client and location at time can access
controllable objects and they remain reserved until the previously started control
operation is first completed by the client. Control access with IEC 61850 originator
category station is interpreted as remote access.
LOCAL
OFF
IEC 61850
IEC 61850
IEC 61850
remote
remote
remote
IED
IED
L/R state
CTRL.LLN0.LocKeyHMI
0
1
0
2
0
Section 3
Basic functions
Control access
Local user
IEC 61850 client
x
1)
x
103