1MRS758407 B
3.2.2
SMU615
Technical Manual
Fault indication
Internal Fault
ROM error
Internal Fault
EEPROM error
Internal Fault
FPGA error
Internal Fault
RTC error
Internal Fault
COM card error
For further information on internal fault indications, see the operation manual.

Warnings

In case of a warning, the merging unit continues to operate except for those functions
possibly affected by the fault, and the green Ready LED remains lit as during normal
operation.
An event about the warnings are stored with the text Warning additionally provided
with the name of the warning, a numeric code and the date and time on the WHMI.
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Table 19:
Warning indications and codes
Warning indication
Warning
Watchdog reset
Warning
Power down det.
Warning
IEC61850 error
Warning
Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning
Logic error
Warning
SMT logic error
Table continues on next page
Fault code
Additional information
81
Error in the ROM memory on the CPU
card.
82
Error in the EEPROM memory on the CPU
card.
83
Error in the FPGA on the CPU card.
84
Error in the RTC on the CPU card.
116
Error in the COM card.
Warning code
Additional information
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has dropped
too low.
20
Error when building the IEC 61850 data
model.
24
Error in the Data set(s).
25
Error in the Report control block(s).
26
Error in the GOOSE control block(s).
27
Error in the SCL configuration file or the file
is missing.
28
Too many connections in the
configuration.
29
Error in the SMT connections.
Section 3
Basic functions