Qty_Goose_Comm Function Block; Function Block; Functionality; Signals - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
3.12.3
3.12.3.1
3.12.3.2
3.12.3.3
SMU615
Technical Manual
Table 56:
QTY_BAD Output signals
Name
Type
OUT
BOOLEAN

QTY_GOOSE_COMM function block

Function block

GUID-0FDC082E-C9A8-4B02-9878-6C49E44B7C0E V1 EN
Figure 37:
Function block

Functionality

The QTY_GOOSE_COMM function block evaluates the peer device communication
status from the quality bits of the input signal and passes it as a Boolean signal to the
application.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the communication status of the GOOSE function block.
When the output is in the true (1) state, the GOOSE communication is active. The
value false (0) indicates communication timeout.

Signals

Table 57:
QTY_GOOSE_COMM Input signals
Name
Type
IN
Any
Table 58:
QTY_GOOSE_COMM Output signals
Name
COMMVALID
Description
Output signal
Default
0
Type
BOOLEAN
Section 3
Basic functions
Description
Input signal
Description
Output signal
69