Table 305:
Electromagnetic compatibility tests
Description
Slow damped oscillatory wave
immunity test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Conducted immunity test
Radiated electromagnetic field
immunity test
Electrical fast transient/burst
immunity test
Surge immunity test
Communication
Other ports
Power frequency magnetic field
immunity test
Continuous
1...3 s
Pulse magnetic field immunity
test
Table continues on next page
Merging unit and functionality tests
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (rms)
f = 150 kHz...80 MHz
20 V/m (rms)
f = 80 MHz...1 GHz; 1.4...2.7
GHz
4 kV
0.5 kV, line-to-earth
1 kV, line-to-earth
2 kV, line-to-earth
0.5 kV, line-to-earth
1 kV, line-to-earth
2 kV, line-to-earth
0.5 kV, line-to-line
1 kV, line-to-line
300 A/m
1000 A/m
1000 A/m
6.4/16 µs
Section 12
Reference
IEC 60255-26:2013
IEC 61000-4-18:2006+A1:2010
ANSI/IEEE C37.90.1-2012
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-2:2008
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-6:2008
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-3:2006
ANSI/IEEE C37.90.2-2004
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-4:2012
ANSI/IEEE C37.90.1-2012
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-5:2005
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-8:2009
GB 14598.26-2015
IEC 61000-4-9:2001
GB 14598.26-2015