1MRS758407 B
Section 12
SMU615
Technical Manual
Merging unit and functionality tests
Table 305:
Electromagnetic compatibility tests
Description
Slow damped oscillatory wave
immunity test
•
Common mode
•
Differential mode
Electrostatic discharge test
•
Contact discharge
•
Air discharge
Conducted immunity test
Radiated electromagnetic field
immunity test
Electrical fast transient/burst
immunity test
Surge immunity test
•
Communication
•
Other ports
Power frequency magnetic field
immunity test
•
Continuous
•
1...3 s
Pulse magnetic field immunity
test
Table continues on next page
Merging unit and functionality tests
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (rms)
f = 150 kHz...80 MHz
20 V/m (rms)
f = 80 MHz...1 GHz; 1.4...2.7
GHz
4 kV
0.5 kV, line-to-earth
1 kV, line-to-earth
2 kV, line-to-earth
0.5 kV, line-to-earth
1 kV, line-to-earth
2 kV, line-to-earth
0.5 kV, line-to-line
1 kV, line-to-line
300 A/m
1000 A/m
1000 A/m
6.4/16 µs
Section 12
Reference
IEC 60255-26:2013
IEC 61000-4-18:2006+A1:2010
ANSI/IEEE C37.90.1-2012
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-2:2008
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-6:2008
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-3:2006
ANSI/IEEE C37.90.2-2004
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-4:2012
ANSI/IEEE C37.90.1-2012
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-5:2005
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-8:2009
GB 14598.26-2015
IEC 61000-4-9:2001
GB 14598.26-2015
245