"Follow-F": Follow Signal, Flashing
Similar to "Follow-S", but instead the LED is flashing when the input is active, Non-
latched.
"Latched-S": Latched, ON
This mode is a latched function. At the activation of the input signal, the alarm shows
a steady light. After acknowledgement by the local operator pressing any key on the
keypad, the alarm disappears.
Activating
signal
LED
Acknow.
GUID-055146B3-780B-43E6-9E06-9FD8D342E881 V1 EN
Figure 17:
Operating sequence "Latched-S"
"LatchedAck-F-S": Latched, Flashing-ON
This mode is a latched function. At the activation of the input signal, the alarm starts
flashing. After acknowledgement, the alarm disappears if the signal is not present and
gives a steady light if the signal is present.
Activating
signal
LED
Acknow.
GUID-1B1414BD-2535-40FA-9642-8FBA4D19BA4A V1 EN
Figure 18:
Operating sequence "LatchedAck-F-S"

Signals

Table 20:
Input signals
Name
Type
OK
BOOLEAN
ALARM
BOOLEAN
RESET
BOOLEAN
Table continues on next page
Default
Description
0=False
Ok input for LED 1
0=False
Alarm input for LED 1
0=False
Reset input for LED 1
Section 3
Basic functions
41