Monitored Data - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
Table 266:
ESXSWI Non group settings (Basic)
Parameter
Values (Range)
Operation
Select timeout
Pulse length
Control model
Operation timeout
Identification
Table 267:
ESXSWI Non group settings (Advanced)
Parameter
Values (Range)
Operation counter
Adaptive pulse
Event delay
Vendor
Serial number
Model
8.1.8
SMU615
Technical Manual
Unit
1=on
5=off
10000...300000
ms
10...60000
ms
0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
10...60000
ms
Unit
0...10000
0=False
1=True
0...60000
ms

Monitored data

Table 268:
CBXCBR Monitored data
Name
POSITION
Table 269:
DCXSWI Monitored data
Name
POSITION
Step
Default
1=on
10000
30000
1
100
4=sbo-with-
enhanced-security
1
30000
ESXSWI1 switch
position
Step
Default
1
0
1=True
1
10000
0
0
0
Type
Values (Range)
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Type
Values (Range)
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Section 8
Control functions
Description
Operation mode on/off
Select timeout in ms
Open and close pulse length
Select control model
Timeout for negative termination
Control Object identification
Description
Breaker operation cycles
Stop in right position
Event delay of the intermediate position
External equipment vendor
External equipment serial number
External equipment model
Unit
Description
Apparatus position
indication
Unit
Description
Apparatus position
indication
223