ABB Relion SMU615 Technical Manual page 38

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Section 3
Basic functions
Parameter
Amplitude Corr C
Division ratio
Voltage input type
Angle Corr A
Angle Corr B
Angle Corr C
Table 8:
Authorization settings
Parameter
Remote Update
Secure Communication
Authority logging
Remote override
Remote viewer
Remote operator
Remote engineer
Remote administrator
Local viewer
Local operator
Local engineer
Local administrator
1) Authorization override is disabled, communication tools ask password to enter the merging unit.
2) Authorization override is enabled, communication tools do not need password to enter the merging unit, except for WHMI which always
requires it.
Table 9:
Binary input settings
Parameter
Threshold voltage
Input osc. level
Input osc. hyst
32
Values (Range)
Unit
0.9000...1.1000
1000...20000
1=Voltage trafo
3=CVD sensor
-20.0000...20.0000
deg
-20.0000...20.0000
deg
-20.0000...20.0000
deg
Values (Range)
Unit
0=Disable
1=Enable
0=False
1=True
1=None
2=Configuration
change
5=Settings edit
6=All
1)
0=False
2)
1=True
Values (Range)
Unit
16...176
Vdc
2...50
events/s
2...50
events/s
Step
Default
0.0001
1.0000
1
10000
1=Voltage trafo
0.0001
0.0000
0.0001
0.0000
0.0001
0.0000
Step
Default
0=Disable
1=True
1=None
1=True
0
0
0
0
0
0
0
0
Step
Default
2
16
1
30
1
10
1MRS758407 B
Description
Phase C Voltage phasor magnitude
correction of an external voltage
transformer
Voltage sensor division ratio
Type of the voltage input
Phase A Voltage phasor angle correction
of an external voltage transformer
Phase B Voltage phasor angle correction
of an external voltage transformer
Phase C Voltage phasor angle correction
of an external voltage transformer
Description
Remote update
Secure Communication
Authority logging level
Disable authority
Set password
Set password
Set password
Set password
Set password
Set password
Set password
Set password
Description
Binary input threshold voltage
Binary input oscillation suppression
threshold
Binary input oscillation suppression
hysteresis
Technical Manual
SMU615

Advertisement

Table of Contents
loading

Table of Contents