Function Block; Signals; Settings - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
7.1.9.2
7.1.9.3
7.1.9.4
Table 240:
VSMSQI Non group settings (Basic)
Parameter
Values (Range)
Operation
Ps Seq V Hi high Lim
Ps Seq V high limit
Ps Seq V low limit
Ps Seq V low low Lim
Ps Seq V deadband
Ng Seq V Hi high Lim
Ng Seq V High limit
Ng Seq V low limit
Ng Seq V low low Lim
Ng Seq V deadband
Table continues on next page
SMU615
Technical Manual

Function block

GUID-63393283-E2C1-406A-9E70-847662D83CFC V2 EN
Figure 126:
Function block

Signals

Table 239:
VSMSQI Input signals
Name
U
0
U
1
U
2

Settings

Unit
1=on
5=off
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
100...100000
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
100...100000
Type
Default
Description
SIGNAL
0
Zero sequence voltage
SIGNAL
0
Positive phase sequence voltage
SIGNAL
0
Negative phase sequence voltage
Step
Default
1=on
1
1.40
1
1.20
1
0.00
1
0.00
1
10000
1
0.20
1
0.05
1
0.00
1
0.00
1
10000
Section 7
Measurement functions
Description
Operation Off / On
High alarm voltage limit for positive
sequence voltage
High warning voltage limit for positive
sequence voltage
Low warning voltage limit for positive
sequence voltage
Low alarm voltage limit for positive
sequence voltage
Deadband configuration value for positive
sequence voltage for integral calculation.
(percentage of difference between min
and max as 0,001 % s)
High alarm voltage limit for negative
sequence voltage
High warning voltage limit for negative
sequence voltage
Low warning voltage limit for negative
sequence voltage
Low alarm voltage limit for negative
sequence voltage
Deadband configuration value for
negative sequence voltage for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
195

Advertisement

Table of Contents
loading

Table of Contents