Section 3 Basic Functions; General Parameters - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
Section 3
3.1
Table 5:
Analog input settings, phase currents
Parameter
Values (Range)
Primary current
Secondary current
Amplitude Corr A
Amplitude Corr B
Amplitude Corr C
Nominal current
Rated secondary Val
Reverse polarity
Table 6:
Analog input settings, residual current
Parameter
Values (Range)
Primary current
Secondary current
Amplitude Corr
Reverse polarity
Table 7:
Analog input settings, phase voltages
Parameter
Values (Range)
Primary voltage
Secondary voltage
VT connection
Amplitude Corr A
Amplitude Corr B
Table continues on next page
SMU615
Technical Manual
Basic functions

General parameters

Unit
1.0...6000.0
A
2=1A
3=5A
0.9000...1.1000
0.9000...1.1000
0.9000...1.1000
39...4000
A
1.000...150.000
mV/Hz
0=False
1=True
Unit
1.0...6000.0
A
1=0.2A
2=1A
0.9000...1.1000
0=False
1=True
Unit
0.100...440.000
kV
60...210
V
1=Wye
2=Delta
0.9000...1.1000
0.9000...1.1000
Step
Default
0.1
100.0
2=1A
0.0001
1.0000
0.0001
1.0000
0.0001
1.0000
1
1300
0.001
3.000
0=False
Step
Default
0.1
100.0
2=1A
0.0001
1.0000
0=False
Step
Default
0.001
20.000
1
100
2=Delta
0.0001
1.0000
0.0001
1.0000
Section 3
Basic functions
Description
Rated primary current
Rated secondary current
Phase A amplitude correction factor
Phase B amplitude correction factor
Phase C amplitude correction factor
Network Nominal Current (In)
Rated Secondary Value (RSV) ratio
Reverse the polarity of the phase CTs
Description
Primary current
Secondary current
Amplitude correction
Reverse the polarity of the residual CT
Description
Primary rated voltage
Secondary rated voltage
Voltage transducer measurement
connection
Phase A Voltage phasor magnitude
correction of an external voltage
transformer
Phase B Voltage phasor magnitude
correction of an external voltage
transformer
31