SMU615
Technical Manual
IEC 61850-9-2 LE sampled values sending SMVSENDER
Functionality
The SMVSENDER function block is used for activating the SMV sending
functionality. It adds/removes the sampled value control block and the related data set
into/from the sending device's configuration. It has no input or output signals.
SMVSENDER can be disabled with the Operation setting value "off". If the
SMVSENDER is disabled from the front port WHMI, it can only be enabled from the
front port WHMI. When disabled, the sending of the samples values is disabled.
Settings
Unit
xLTxTR function block
Function block
ILTCTR
ULTVTR
MINCB_OPEN
GUID-73D3A1AC-39AD-4181-83A6-A01BCE20088A V1 EN
Figure 27:
Function block
Operation principle
The MINCB_OPEN input signal is supposed to be connected through a binary input to
the NC auxiliary contact of the miniature circuit breaker protecting the VT secondary
circuit. The MINCB_OPEN signal sets the FUSEF_U output signal to block all the
voltage-related functions when MCB is in the open state.
Signals
Table 41:
ULTVTR1_vt Input signals
Name
Type
MINCB_OPEN
BOOLEAN
Step
Default
1=on
Default
Description
0=False
Active when external MCB opens protected voltage
circuit
Section 3
Basic functions
Description
Operation
61