Section 3
Basic functions
3.13.1.7
3.13.1.8
82
Settings
The function does not have any parameters available in PCM600.

R_TRIG function block

Function block
GUID-3D0BBDC3-4091-4D8B-A35C-95F6289E6FD8 V1 EN
Figure 50:
Function block
Functionality
R_TRIG is used as a rising edge detector.
R_TRIG detects the transition from FALSE to TRUE at the CLK input. When the
rising edge is detected, the element assigns the output to TRUE. At the next execution
round, the output is returned to FALSE despite the state of the input.
Signals
Table 94:
R_TRIG Input signals
Name
Type
CLK
BOOLEAN
Table 95:
R_TRIG Output signal
Name
Q
Settings
The function does not have any parameters available in PCM600.

F_TRIG function block

Function block
GUID-B47152D2-3855-4306-8F2E-73D8FDEC4C1D V1 EN
Figure 51:
Function block
Functionality
F_TRIG is used as a falling edge detector.
Default
0
Type
BOOLEAN
1MRS758407 B
Description
Input signal
Description
Output signal