ABB Relion SMU615 Technical Manual page 215

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
SMU615
Technical Manual
Parameter
Values (Range) Unit
Storage rate
32, 16, 8
Periodic trig
0...604 800
time
Stor. mode
0=Waveform
periodic
1=Trend /
cycle
Stor. mode
0=Waveform
manual
1=Trend /
cycle
Table 251:
RDRE Non-group binary channel settings
Parameter
Values (Range) Unit
Operation
1=on
5=off
Level trigger
1=Positive or
mode
Rising
2=Negative or
Falling
3=Both
4=Level
trigger off
Storage mode
0=Waveform
1=Trend /
cycle
Channel id
0 to 64
text
characters,
alphanumeric
Table 252:
RDRE Control data
Parameter
Values (Range) Unit
Trig recording
0=Cancel
1=Trig
Clear
0=Cancel
recordings
1=Clear
Measurement functions
Step
samples per
fundamental
cycle
s
10
1
1
Step
1
1
1
Step
Section 7
Default
Description
32
Storage rate
of the
waveform
recording
0
Time between
periodic
triggerings
0
Storage mode
for periodic
triggering
0
Storage mode
for manual
triggering
Default
Description
5=off
Binary
channel is
enabled or
disabled
1=Rising
Level trigger
mode for the
binary
channel
0
Storage mode
for the binary
channel
DR binary
Identification
channel X
text for the
analog
channel used
in the
COMTRADE
format
Default
Description
Trigger the
disturbance
recording
Clear all
recordings
currently in
memory
209