Application

All trip signals from GOOSE signals are routed through the trip logic. The most
simplified application of the logic function is linking the trip signal and ensuring that
the signal is long enough.
The tripping logic in the merging unit is intended to be used in the three-phase tripping
for all fault types (3ph operating). To prevent the closing of a circuit breaker after a
trip, TRPPTRC can block the CBXCBR closing.
TRPPTRC is intended to be connected to one trip coil of the corresponding circuit
breaker. If tripping is needed for another trip coil or another circuit breaker which
needs, for example, different trip pulse time, another trip logic function can be used.
The two instances of the PTRC function are identical, only the names of the functions,
TRPPTRC1 and TRPPTRC2, are different. Therefore, even if all references are made
only to TRPPTRC1, they also apply to TRPPTRC2.
The inputs from the GOOSE signal are connected to the OPERATE input. The TRIP
output is connected to the binary outputs on the IO board. This signal can also be used
for other purposes within the merging unit, for example when starting the breaker
failure protection.
TRPPTRC is used for simple three-phase tripping applications.
GOOSERCV_BIN 0_MASTER_TRIP 1
GOOSERCV_BIN 10_MASTER_TRIP 1
GUID-740654EE-6788-488B-AEF1-E77BA5851D16 V1 EN
Figure 82:
Typical TRPPTRC connection

Signals

Table 164:
TRPPTRC Input signals
Name
Type
BLOCK
BOOLEAN
OPERATE
BOOLEAN
RST_LKOUT
BOOLEAN
Protection related functions
OR
B1
O
B2
BLOCK
O:28|T:2.5|I:1
OPERATE
RST_LKOUT
GENERAL_LOCKOUT_RESET
Default
Description
0=False
Block of function
0=False
Operate
0=False
Input for resetting the circuit breaker lockout
function
Section 4
TRPPTRC1
TRIP
TRPPTRC1_TRIP
CL_LKOUT
O:33|T:2.5|I:1
121