Monitored Data - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
7.2.6
SMU615
Technical Manual
Parameter
Values (Range) Unit
High trigger
0.00...60.00
level
Low trigger
0.00...2.00
level
Storage mode
0=Waveform
1=Trend /
cycle
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of
the corresponding analog channel.

Monitored data

Table 254:
RDRE Monitored data
Parameter
Values (Range) Unit
Number of
0...100
recordings
Rem. amount
0...100
of rec.
Rec. memory
0...100
used
Time to
0...604 800
trigger
Measurement functions
Step
pu
0.01
pu
0.01
1
Step
%
s
Section 7
Default
Description
10.00
High trigger
level for the
analog
channel
0.00
Low trigger
level for the
analog
channel
0
Storage mode
for the analog
channel
Default
Description
Number of
recordings
currently in
memory
Remaining
amount of
recordings
that fit into the
available
recording
memory, when
current
settings are
used
Storage mode
for the binary
channel
Time
remaining to
the next
periodic
triggering
211