ABB Relion SMU615 Technical Manual page 182

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Section 7
Measurement functions
176
GUID-63CA9A0F-24D8-4BA8-A667-88632DF53284 V1 EN
Figure 119:
Integral deadband supervision
The deadband value used in the integral calculation is configured with the X deadband
setting. The value represents the percentage of the difference between the maximum
and minimum limit in the units of 0.001 percent x seconds.
The reporting delay of the integral algorithms in seconds is calculated with the
formula:
(max min)
deadband
×
t s
( )
=
100
%
Y
×
GUID-5381484E-E205-4548-A846-D3519578384B V1 EN
Example for CMMXU:
A deadband = 2500 (2.5% of the total measuring range of 40)
I_INST_A = I_DB_A = 0.30
If I_INST_A changes to 0.40, the reporting delay is:
(
40 0
)
2500 1000
/
×
t s
( )
=
0 40 0 30 100
.
.
%
×
GUID-D1C387B1-4F2E-4A28-AFEA-431687DDF9FE V1 EN
Table 205:
Parameters for deadband calculation
Function
Three-phase current
measurement (CMMXU)
Three-phase voltage
measurement (VMMXU)
Residual current measurement
(RESCMMXU)
Frequency measurement
(FMMXU)
Table continues on next page
/
1000
10
s
=
Settings
A deadband
V Deadband
A deadband res
F deadband
1MRS758407 B
(Equation 8)
Maximum/minimum (=range)
40/0 (=40xIn)
4/0 (=4xUn)
40/0 (=40xIn)
75/35 (=40 Hz)
1)
SMU615
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents