ABB Relion SMU615 Technical Manual page 222

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Section 8
Control functions
216
ENA_CLOSE
AU_CLOSE
Communication
SYNC_OK
SYNC_ITL_BYP
POSCLOSE
TRIP
Operation timeout elapses
GUID-CE930980-4EFF-46E7-B7C2-81E1A203800C V1 EN
Figure 131:
Condition for enabling the close request (CL_REQ) for CBXCBR
When the open command is given from communication, by activating the AU_OPEN
input, it is processed only if OPEN_ENAD is TRUE. OP_REQ output is also available.
ENA_OPEN
AU_OPEN
Communication
POSCLOSE
Operation timeout elapses
GUID-25D427CB-5D32-4F30-93BF-29779C9DCB5B V1 EN
Figure 132:
Condition for enabling the open request (OP_REQ) for CBXCBR
OPEN and CLOSE outputs
The EXE_OP output is activated when the open command is given (AU_OPEN, via
communication) and OPEN_ENAD signal is TRUE. In addition, the protection trip
commands can be routed through the CBXCBR function by using the TRIP input.
When the TRIP input is TRUE, the EXE_OP output is activated immediately and
bypassing all enabling or blocking conditions.
The EXE_CL output is activated when the close command is given (AU_CLOSE, via
communication) and CLOSE_ENAD signal is TRUE. When the TRIP input is
"TRUE", CB closing is not allowed.
AND
SET
SR
OR
RESET
OR
AND
SET
SR
RESET
OR
OR
1MRS758407 B
CL_REQ
OP_REQ
SMU615
Technical Manual