Basic functions
3.1.6

Binary input settings

Table 12: Binary input settings
Parameter
Values (Range)
Threshold voltage
16...176
Input osc. level
2...50
Input osc. hyst
2...50
3.1.7

Binary signals in card location Xnnn

Table 13: Binary input signals in card location Xnnn
Name
Xnnn-Input m
Table 14: Binary output signals in card location Xnnn
Name
Xnnn-Pmm
1
Xnnn = Slot ID, for example, X100, X110, as applicable
2
Pmm = For example, PO1, PO2, SO1, SO2, as applicable
46
Unit
Vdc
events/s
events/s
Adjust the binary input threshold voltage correctly. The threshold voltage
should be comparable to the nominal value instead of the default
minimum value. The factory default is 16 V to ensure the binary inputs'
operation regardless of the auxiliary voltage used (24, 48, 60, 110, 125,
220 or 250 V DC). However, the default value is not optimal for the
higher auxiliary voltages. The binary input threshold voltage should be
set as high as possible to prevent any inadvertent activation of the binary
inputs due to possible external disturbances. At the same time, the
threshold should be set so that the correct operation is not jeopardized
in case of undervoltage of the auxiliary voltage.
Type
1
BOOLEAN
Type
1 2
BOOLEAN
Step
Default
2
16
1
30
1
10
Default
0=False
1MRS758755 C
Description
Binary input
threshold voltage
Binary input oscil-
lation suppression
threshold
Binary input oscil-
lation suppression
hysteresis
Description
Description
See the application
engineering guide for
terminal connections
REC615 & RER615
Technical Manual