Section 4
Protection related functions
4.1.7
Table 166:
TRPPTRC Non group settings (Basic)
Parameter
Operation
Trip pulse time
Trip output mode
4.1.8
4.1.9
122
Table 165:
TRPPTRC Output signals
Name
TRIP
CL_LKOUT

Settings

Values (Range)
Unit
1=on
5=off
20...60000
ms
1=Non-latched
2=Latched
3=Lockout

Monitored data

Table 167:
TRPPTRC Monitored data
Name
TRPPTRC

Technical revision history

Table 168:
TRPPTRC Technical revision history
Technical revision
B
C
D
E
F
Type
Description
BOOLEAN
General trip output signal
BOOLEAN
Circuit breaker lockout output (set until reset)
Step
Default
1=on
1
250
1=Non-latched
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Change
-
-
Internal improvement.
Setting
changed to "Latched".
Internal improvement.
1MRS758407 B
Description
Operation Off / On
Minimum duration of trip output signal
Select the operation mode for trip output
Unit
Description
Status
Trip output mode default setting is
Technical Manual
SMU615