Functionality

The GOOSERCV_INTL function is used to connect the GOOSE double binary input
to the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.

Signals

Table 50:
GOOSERCV_INTL Output signals
Name
Type
POS_OP
BOOLEAN
POS_CL
BOOLEAN
POS_OK
BOOLEAN
VALID
BOOLEAN

GOOSERCV_ENUM function block

Function block

GUID-E1AE8AD3-ED99-448A-8C11-558BCA68CDC4 V1 EN
Figure 33:
Function block
Functionality
The GOOSERCV_ENUM function block is used to connect GOOSE enumerator
inputs to the application.
Signals
Table 51:
GOOSERCV_ENUM Output signals
Name
Type
OUT
Enum
VALID
BOOLEAN
Description
Position open output signal
Position closed output signal
Position OK output signal
Output signal
Description
Output signal
Output signal
1MRS758407 B