Section 12
Merging unit and functionality tests
246
Description
Damped oscillatory magnetic
field immunity test
2 s
1 MHz
A.C. and D.C. voltage dips and
interruptions test
Power frequency immunity test
Common mode
Differential mode
Emission tests
Conducted
0.15...0.50 MHz
0.5...30 MHz
Radiated
30...230 MHz
230...1000 MHz
1...3 GHz
3...6 GHz
Table 306:
Insulation tests
Description
Dielectric tests
Impulse voltage test
Insulation resistance
measurements
Type test value
100 A/m
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Binary inputs only
300 V rms
150 V rms
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak,
measured at 10m distance
<47 dB (µV/m) quasi peak,
measured at 10m distance
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3m distance
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3m distance
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min,
communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
>100 MΩ, 500 V DC
1MRS758407 B
Reference
IEC 61000-4-10:2001
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-11:2004
IEC 61000-4-29:2000
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-16:1998+A2:2009
GB 14598.26-2015
IEC 60255-26:2013
CISPR 11:2009+A1:2010
CISPR 22:2008
GB 14598.26-2015
Reference
IEC 60255-272013
IEC 60255-272013
IEC 60255-272013
SMU615
Technical Manual