ABB Relion SMU615 Technical Manual page 247

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
SMU615
Technical Manual
Description
Power consumption
Threshold voltage
Reaction time
Adjust the binary input threshold voltage correctly. The threshold
voltage should be set to 70% of the nominal auxiliary voltage. The
factory default is 16 V to ensure the binary inputs' operation
regardless of the auxiliary voltage used (24, 48, 60, 110, 125, 220 or
250 V DC). However, the default value is not optimal for the higher
auxiliary voltages. The binary input threshold voltage should be set as
high as possible to prevent any inadvertent activation of the binary
inputs due to possible external disturbances. At the same time, the
threshold should be set so that the correct operation is not jeopardized
in case of undervoltage of the auxiliary voltage.
Table 295:
Signal output X100: SO1
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load
Table 296:
Signal outputs and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load
Technical data
Value
31.0...570.0 mW
16...176 V DC
<3 ms
Value
250 V AC/DC
5 A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
Value
250 V AC/DC
5 A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
Section 11
241