application logic quality bit propagation, each (simple and even combined) signal has
quality which can be evaluated.
The OUT output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.
Signals
Table 53:
QTY_GOOD Input signals
Name
Type
IN
Any
Table 54:
QTY_GOOD Output signals
Name
Type
OUT
BOOLEAN
QTY_BAD function block
Function block
GUID-8C120145-91B6-4295-98FB-AE78430EB532 V1 EN
Figure 36:
Function block
Functionality
The QTY_BAD function block evaluates the quality bits of the input signal and passes
it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function output,
binary input, application function output or received GOOSE signal). Due to
application logic quality bit propagation, each (simple and even combined) signal has
quality which can be evaluated.
The OUT output indicates quality bad of the input signal. Input signals that have any
other than test bit set, will indicate quality bad status.
Signals
Table 55:
QTY_BAD Input signals
Name
Type
IN
Any
Default
Description
0
Input signal
Description
Output signal
Default
Description
0
Input signal