Application Configuration And Test Mode; Control Mode - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
3.5.3
3.5.4
SMU615
Technical Manual
Table 28:
Test mode
Test mode
Description
Normal mode
Normal operation
IED blocked
Function working as in "Normal mode" but ACT
configuration can be used to block physical
outputs to process. Control function commands
blocked.
IED test
Function working as in "Normal mode" but in
parallel with test parameters.
IED test and blocked
Function working as in "Normal mode" but in
parallel with test parameters. ACT configuration
can be used to block physical outputs to process.
Control function commands blocked.
Behavior data objects in all logical nodes follow LD0.LLN0.Mod
value. If "Normal mode" is selected, behaviour data objects follow
mode (.Mod) data object of the corresponding logical device.
Vertical and horizontal communication is not blocked by the "IED
blocked" or "IED test and blocked" modes.

Application configuration and Test mode

The physical outputs from control commands to process are blocked with "IED
blocked" and "IED test and blocked" modes. If physical outputs need to be blocked
from the other functions, the application configuration must be used to block these
signals. Blocking scheme needs to use BEH_BLK output of TEST_MODE function
block.

Control mode

The mode of all logical nodes located under CTRL logical device can be set with
Control mode. The Control mode parameter is available via the HMI or PCM600 path
Configuration/Control/General. By default, Control mode can only be set through
WHMI via front port RJ-45.Control mode inherits its value from Test mode but
Control mode "On", "Blocked" and "Off" can also be set independently. Control
mode is also available via IEC 61850 communication (CTRL.LLN0.Mod).
Table 29:
Control mode
Control mode
On
Blocked
Off
Description
Normal operation
Control function commands blocked
Control functions disabled
Section 3
Basic functions
TEST_MODE BEH_BLK
FALSE
TRUE
FALSE
TRUE
Control BEH_BLK
FALSE
TRUE
FALSE
49

Advertisement

Table of Contents
loading

Table of Contents