Section 3
Basic functions
3.13.1.4
3.13.1.5
80
NOT function block
Function block
GUID-0D0FC187-4224-433C-9664-908168EE3626 V1 EN
Figure 47:
Function block
Functionality
NOT is used to generate combinatory expressions with Boolean variables.
NOT inverts the input signal.
Signals
Table 88:
NOT Input signal
Name
Type
I
BOOLEAN
Table 89:
NOT Output signal
Name
O
Settings
The function does not have any parameters available in PCM600.
MAX3 function block
Function block
GUID-5454FE1C-2947-4337-AD58-39D266E91993 V1 EN
Figure 48:
Function block
Functionality
The maximum function MAX3 selects the maximum value from three analog values.
Disconnected inputs and inputs whose quality is bad are ignored. If all inputs are
disconnected or the quality is bad, MAX3 output value is set to -2^21.
Default
0
Type
BOOLEAN
1MRS758407 B
Description
Input signal
Description
Output signal
SMU615
Technical Manual