ABB Relion SMU615 Technical Manual page 248

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Section 11
Technical data
242
Table 297:
Double-pole power output relays with TCS function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC (two
contacts connected in series)
Minimum contact load
Trip-circuit supervision (TCS):
Control voltage range
Current drain through the supervision circuit
Minimum voltage over the TCS contact
Table 298:
Single-pole power output relays
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load
Table 299:
High-speed output HSO with BIO0007
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
Operate time
Reset
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
Value
250 V AC/DC
6 A
15 A
30 A
5 A/3 A/1 A
<1 ms
<20 ms, resistive load
1MRS758407 B
SMU615
Technical Manual