Signals - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Section 3
Basic functions
3.13.9.3
110
GUID-F0078144-A40B-4A72-915A-0E6665F8DEB1 V1 EN
Figure 77:
Operation in "Toggle" mode
The BLOCK input can be used for blocking the functionality of the outputs. The
operation of the BLOCK input depends on the Operation mode setting. If Operation
mode is "Toggle", the output state freezes and cannot be changed while the BLOCK
input is active. If Operation mode is "Pulsed", the activation of the BLOCK input resets
the outputs to the "False" state and further control requests are ignored while the
BLOCK input is active.
From the remote communication point of view SPCGAPC toggled
operation mode is always working as persistent mode. The output O#
follows the value written to the input IN#.

Signals

Table 154:
SPCGAPC Input signals
Name
Type
BLOCK
BOOLEAN
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
IN14
BOOLEAN
IN15
BOOLEAN
IN16
BOOLEAN
Default
Description
0=False
Block signal for activating the blocking mode
0=False
Input of control point 1
0=False
Input of control point 2
0=False
Input of control point 3
0=False
Input of control point 4
0=False
Input of control point 5
0=False
Input of control point 6
0=False
Input of control point 7
0=False
Input of control point 8
0=False
Input of control point 9
0=False
Input of control point 10
0=False
Input of control point 11
0=False
Input of control point 12
0=False
Input of control point 13
0=False
Input of control point 14
0=False
Input of control point 15
0=False
Input of control point 16
1MRS758407 B
SMU615
Technical Manual