ABB Relion SMU615 Technical Manual page 253

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
SMU615
Technical Manual
Table 307:
Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Table 308:
Environmental tests
Description
Dry heat test
Dry cold test
Damp heat test
Change of temperature test
Table 309:
Product safety
Description
LV directive
Standard
Table 310:
EMC compliance
Description
EMC directive
Standard
Merging unit and functionality tests
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1: 1988
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2: 1988
Type test value
96 h at +55ºC
16 h at +85ºC
96 h at -25ºC
16 h at -40ºC
6 cycles (12 h + 12 h) at
+25°C...+55°C, humidity
>93%
5 cycles (3 h + 3 h) at
-25°C...+55°C
Reference
2006/95/EC
EN 60255-27 (2013)
EN 60255-1 (2009)
Reference
2004/108/EC
EN 60255-26 (2013)
Section 12
Requirement
Class 2
Class 2
Reference
IEC 60068-2-2:2007
IEC 60068-2-1:2007
IEC 60068-2-30:2005
IEC 60068-2-14:2009
247