Communication - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
2.5
SMU615
Technical Manual
Audit trail event
Firmware change fail
Attached to retrofit test case
Removed from retrofit test case
Control remote
Test on
Test off
Reset trips
Time change
View audit log
Login
Logout
Password change
Firmware reset
Violation local
Violation remote

Communication

The merging unit supports a range of communication protocols including IEC 61850
and IEC 61850-9-2 LE. Operational information and controls are available through
these protocols. However, some communication functionality, for example,
horizontal communication between the merging units, is only enabled by the IEC
61850 communication protocol.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter settings and disturbance recordings can be
accessed using the IEC 61850 protocol. Disturbance recordings are available to any
Ethernet-based application in the IEC 60255-24 standard COMTRADE file format.
The merging unit can send and receive binary signals from other devices (so-called
horizontal communication) using the IEC 61850-8-1 GOOSE profile, where the
highest performance class with a total transmission time of 3 ms is supported.
Furthermore, the merging unit supports sending of analog values using GOOSE
messaging. The merging unit meets the GOOSE performance requirements for
tripping applications in distribution substations, as defined by the IEC 61850
standard.
The merging unit can support five simultaneous clients. If PCM600 reserves one
client connection, only four connections are left for other clients.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The merging unit can be connected to
Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the
fiber-optic LC connector (100Base-FX).
Section 2
SMU615 overview
Authority logging level
23

Advertisement